On Wednesday 16/06/21 we started slow-down tests on the hot water pump of WEB. We have proceded at steps of -5Hz starting from the standard 50Hz supply and switching between the left and right pump in order to check for different responses.
Before the test the following 4 accelerometers have been added:
CHANNEL NAME | ACC TYPE | LOCATION |
ENV_WEB_HOTPUMP_OVER | PCB 393B12 | Attached to the hot pump, at its base platform |
ENV_WEB_COLDPUMP_OVER | PCB 356B18 | Attached to the cold pump, at its base platform |
ENV_WEB_HOTPUMP_FLOOR | Meggit 731-207 | Fixed to the ground, between hot and cold pumps, slightly nearest to the hot |
ENV_WEB_HOTPUMP_PIPE_IN | PCB 393B12 | Attached to an exposed part of the pipeline that goes from the UTA to the boiler |
Before the beginning of operations the right water pump was active, with 50Hz supply
12:28 UTC | we entered the WEB water pumps room |
12:32 UTC | switch from right to left pump, at 50Hz |
12:42 UTC | switch from left to right pump, at 45Hz |
12:51 UTC | switch from right to left pump, at 45Hz |
13:00 UTC | switch from left to right pump, at 40Hz |
13:06 UTC | the security system shut down the boiler (low pressure) |
13:08 UTC | the same right pump (no switch) is slowed at 35Hz |
15:15 UTC | the supply of the right pump is increased from 35Hz at +1Hz steps: at 47Hz the boiler turns on |
15:17 UTC | the supply of the right pump is decreased from 47Hz at -1Hz steps: at 40Hz the boiler turns off |
15:18 UTC | the system is restored at the starting conditions (right pump at 50Hz); we leave the room. |
During the whole process a regular series of glitches from air compressors occurred, every 3 minutes.