Last week the motor of one of the 500 KVA diesel generator (GE 1) hosted in the Technical Building and serving the Central Building + Computing room on UPS and Central Building UTAs on IPS was identified as faulty.
Since it seems that motor repair could be lenghty the immediate solution being pursued at the moment is the renting of an emergency generator to be positioned in the vicinity of the TB that would replace the malfunctioning one and bringing back the standard situation.
This emergency generator has been already shipped onsite (See Fig. 1) and the electrical swap is currently foreseen for tomorrow, Tuesday June 14. The swap itself will not imply IPS interruptions but a test must be done on generator intervention so a ~30 sec ENEL interruption will be simulated.