Reports 1-1 of 1 Clear search Modify search
Infrastructures (Air Conditioning)
soldani - 15:14 Tuesday 06 October 2020 (49582) Print this report
Anti-vibration mounts under End Terminal Bld. boilers
This morning the anti-vibration mounts were installed under the boilers of the terminal buildings.
Tomorrow morning we will proceed with the springs for the fan / return-air motor of the uta of the clean rooms in CEB, similarly to what has already been done for the supply-air one.
Images attached to this report
Comments to this report:
fiori - 12:17 Wednesday 14 October 2020 (49656) Print this report

The installation seems to have succesfully reduced the vibration noise associated to the boiler observed by the guralp sensors,  at the level of the NE and WE towers floor.

It seems to appreciate a little residual at NEB. Yet, there might be margin for a further improvement, since as Davide observed, some springs appeared overloaded and possibly short-circuited.

Images attached to this comment
Search Help
×