Reports 1-1 of 1 Clear search Modify search
AdV-TCS (Subsystem management)
gherardini - 13:59 Saturday 11 November 2017 (40010) Print this report
WI laser switch-off
This morning at 11:56utc the WI CO2 laser had been switched off by the over temperature protection (see plot), I came on site to check the status of the system: the WI chiller was complaining about "motor fault" so I put the system in safety condition: RF driver unplugged and chiller switched off.
Images attached to this report
Comments to this report:
rocchi - 23:41 Sunday 12 November 2017 (40013) Print this report

Here is a plot of the last moments before the shutdown. From the time behavior of the power, it seems the problems started around 11:00 UTC.

Images attached to this comment
Ciardelli Menzione Nardecchia Rocchi - 16:06 Tuesday 14 November 2017 (40035) Print this report

This morning we have replaced the WI broken chiller with the new one.

We have also profitted of this intervention to perform a maintenance of the cooling systems of both CO2 lasers (filter cleaning...).

At present both CO2 lasers are ON at full power.