Eric noticed that a noise line around 80Hz (from time to time switching to 85Hz) is affecting the BPC signals: See Figure 1. This noise has a 24h cycle. The same noise is present in magnetic probes and in the ENEL voltage monitors (all three phases): see Figure 2. This made us suspect of some sizeble 3-phase engine powered on ENEL, .... we thought of something related to air conditioning
More precisely, the fundamental frequency of the noise is at 15-20Hz. (Figure 3) and it produces sidebands of 100Hz and harmonics up to 400Hz or so (Figure 4).
The noise correlates well with the EER temperature (Figure 5). We suspect the dual split air conditioner installed in EER in January, maybe it is its compressor unit.
It might be useful to investigate why the similar device installed in IER appears not to produce such evident EM noise...