New version of SL_TempController Tango server

This morning I started a new version (v7r1) on SL_TempController server, adding 4 new channes: PSL_SL_PUMP1_W, PSL_SL_PUMP2_W, PSL_SL_XTAL1_W, PSL_SL_XTAL2_W. This software will in test for a week.

Images attached to this report
Comments to this report:
cleva - 16:31 Friday 07 February 2020 (48388) Print this report

Those signals refer to the correction sent to the TEC to cool down either the pump diod and the crystals of the slave laser.

the correction moves between 0 and 100.

100 means the correction is null and "0" means that the sent correction is maximal.
In the plot we got ~10 which is nearly close to the maximum of correction.

Such high vale may increase the ageing the TEC at some point up to some breakage 

In the past the correction used to be around "50" instead (see attached doc, p2, data for a Xstal temperature setting of 25 °C gives a correction @ OUT from PID of ~50 %)

This would mean that the cooling is by far less efficient. It could be that the water flow is reduced due to the dirts seen in the water cooling system of PSL.

 

Non-image files attached to this comment
G. Ballardin - 10:07 Tuesday 11 February 2020 (48419) Print this report

This software has worked properly for a week. It's now stored into SVN archive (SL_TempController v7r1) and ready to be installed in /virgoApp.

carbognani - 11:40 Tuesday 18 February 2020 (48476) Print this report

Installed in /virgoApp and restarted this morning from there:

fcarbogn@olserver129[~]: ps -ef | grep SL

virgod   19905     1  0 11:27 ?        00:00:00 /virgoApp/SL_TempController/v7r1p0/Linux-x86_64-CL7/SL_TempController EER

 