A few more observations concerning the test of April 23:
- at some point, while the AHU was off, we stopped the water flux by closing the valves located inside the CEB AHU room. Unespectly we measured an increased acoustic noise in the range 50 to 100 Hz (Figure 1)
- between 8:49 and 11:13 UTC, while the AHU was off, we closed all air valves of ducts (all set to 0%). In principle we would expect some change in the position of low frequency spectral peaks, if they were associated to acoustic modes of the air ducts. We did not notice any change (Figure 2).
- acoustic spectrograms show some peaks changing frequency, mostly above a few hundred Hz. They seem correlated to the frequency of the SUPPLY fan (Figures 3 and 4). Yet, we then notice that similar ones are present also when the HVAC was running in MANUAL modes (that is when both fans frequency fixed): Figure 5. Could they be associated to the air flow regulators instead?