Yesterday the B1_PD{1,2}_DC offsets wee adjusted by Romain:
- 2026-04-08-19h18m30-UTC info gouaty SDB2_dbox_bench saved - gouaty: adjust B1_PD2 offset (rev. 269159)
2026-04-08-19h19m45-UTC info gouaty SDB2_dbox_bench saved - gouaty: adjust B1_PD1 offset (rev. 269160)
2026-04-08-19h19m48-UTC info gouaty 'Reload config' sent to SDB2_dbox_bench
After this operation, the SDB2_LC and the SQZ_CTRL became blue in VPM interface complaining about possible missing samples
This morning we made some investigations on the rtpc1 servers
- by changing the TOLM_PROCESSOR_LOOP delays from 25us to 28us and then restarting most of the rtpc1's servers execpt the DaqBox ones
- and then reconfiguring the SDB2_MezzPD0 and the SDB2_MezzPD1 service mezzanines
- but without any improvments
We put back the standard TOLM_PROCESSOR_LOOP value (25us) and we continued with the investigations . We found that
- the SDB1_FAST_SHUTTER server task order can change . To fix its order a dependancy with the SQB1_Quadrants server has been added and now this server is always excuted after the SQB1_Quadrants one . Note that the SQB1_FAST _SERVER is the server driving the OMC dac channels
- re-starting any ACL's server on the rtpc1, is enough to recover the correct running conditions for the 2 faulty servers
At the end, as a simple workaround, a reloadConfig of the SDB_EDB_Tpro server allows recovering the correct running conditions without stopping any ACL's servers