Reports 1-1 of 1 Clear search Modify search
On-call intervention (General)
Oncall-system - 18:20 Sunday 12 October 2025 (67921) Print this report
On-call intervention

The following report has been submitted to the On-call interface.

On-call events -> Air Conditioning

Title: Mode cleaner HVAC. Chiller temperature problem.

Author(s): andreazzoli

Called at: 15:35, 12-10-2025, by: Magazzu
Remote intervention: Started: ; Ended:
On-site intervention: Started: 15:57, 12-10-2025; Ended: 18:30, 12-10-2025
Status: Unresolved
Operator when issue resolved: Zaza

Details:

Contacted Soldani D..
Agreed on the need to perform a check.
Performed check and detected problem on chiller no. 2 due to condensation fan not working. Checked circuit water pressure (ok). Attempted to reset chiller without success. Electrically isolated the faulty fan and covered the fan section to facilitate freon condensation.
Fan replacement required but not available at present. More thorough check required for alarm detected “A1.”
Soldani D. informed.