Test DET HVAC , 23 April 2026 7.52 UTC supply fan: 31.9 Hz return fan: 13.9 Hz 08:02 UTC --> supply and return AHU OFF Air flux velocity- supply air duct: 0 m/s Air flux velocity- return air duct: 0 m/s 08:26 UTC --> Water distribution isolated (hot water valve closed first, followed by the cold water valve, both located in the CEB AHU hall room). P.S. The air duct distribution valves are moving because they are set to automatic mode. 08:49 UTC--> the opening of all supply and return air distribution valves are manually set to 0% (fully closed) 09:10 UTC--> external valves are closed 09:39 UTC (few minute)--> open and close the door of the silenziatore 10:23 UTC --> Water distribution open 10:43-10:46 UTC---> opening and closing of the silencer door 10:53 (1 min) UTC---> tapping on return duct (top) 10:55 (1 min) UTC --> tapping on supply duct (bottom) 11:06 UTC--> opening of the filter after supply fan 11:13 UTC--> all valves (air distribution and external) are opened 11:24 UTC --> supply and return fan switched ON ************************************** Test of supply and return fan speed *** Return fan manually fixed @ 13.8 Hz (10 Hz)*** 13:08 UTC--> supply fan 17 Hz (12.11 Hz) supply air flux velocity: 1.03 m/s return Air flux velocity: 0.1 m/s 13:21 UTC --> supply fan 23 Hz (15.7-16 Hz) supply air flux velocity: 1.49 m/s return Air flux velocity: 0.15 m/s 13:35 UTC --> supply fan 29 Hz (22.6-22.9 Hz) supply air flux velocity: 2.72 m/s return Air flux velocity: 0.33 m/s 13:48 UTC --> supply fan 35 Hz (29.5 Hz) supply air flux velocity: 4.1 m/s - 3.4 m/s (second reading) return Air flux velocity: 1.17m/s - 0.99 m/s (second reading) 14:07 UTC --> nuova sas , supply valve closed 14:15 UTC --> nuova sas , supply valve open 14:25 UTC --> nuova sas , supply valve automatically closed 14:28 UTC --> supply fan 41 Hz (36.5 Hz -36.9 Hz) supply air flux velocity: 4.3 m/s return Air flux velocity: 2.1 m/s 14:43 UTC --> supply fan 50 Hz (46.7 Hz) supply air flux velocity: 4.8 m/s return Air flux velocity: 2.27 m/s 14:55 UTC--> supply fan set to automatic mode 14:57 UTC--> return fan set to automatic mode *** Supply fan manually fixed**** 15:16 UTC ---> supply fan at 30 Hz (24 Hz) return fan 10 Hz (13.8 Hz) 15:19 UTC --> retun fan 17 Hz (18.2 Hz) supply air flux velocity: 2.8 m/s return Air flux velocity: 0.26 m/s 15:31 UTC--> retun fan 27 Hz (26.1 Hz) supply air flux velocity: 2.85 m/s return Air flux velocity: 1.10 m/s 15:45 UTC--> test for the night return fan 10 Hz (13.8 Hz) -- velocity 0.3 m/s supply fan at 33 Hz (27.5 Hz) -- velocity 2.9 m/s