This morning the TB compressor n2 went in alarm mode and stopped (picture n1), we have to understand the failure that probably caused a low oil level therefore we contacted the firm that took care of the maintenance that will be on site as soon as possible. However no problem for the ITF equipment that is under the compressor n1 as usual.
In meanwhile we noticed that the sensor used for monitor the Compressor n2 have a leak, therefore we dismounted and revisioned it on site, now it worked properly (picture n2).
This morning at about 6:30 UTC the burner of the WE heater stopped automatically due to the intervention of the electric thermal protection. After the check of the system the heater has been regulary restarted at about 7:00 UTC (picture attached), no variation in the temperature of the hall.
This morning the external firm performed the semestral maintenance of all the compressors on site, the operations have been completely transparent for the ITF thanks to the presence of double machines.
We always use a pair of water pumps for each water circuits (hot and cold water), one at a time. We have sent back to the company one of the two hot-water pumps of the WEB technical building (the one on the right) for routine maintenance, leaving only the left one running.
On Friday 11 Sept. we put the reiuvenated pump back into operation, taking a short break of the system for the time of the intervention (from 08:00 to 08:30 UTC).
We can see that the maintenance work had the effect of reducing the vibrations transmitted to the WEB seismometer (ENV_WEB_SEIS): the line at 47.2 Hz of the left pump was higher than the line at 47,1 Hz of the right pump.
Some sidebands have also disappeared. Paolo also noted that on the long term (one day) the 47.1 Hz line become even fainter.
Note that even when the pumps were noisy we had spring dampers under them, but their signal was still visible in the WEB seismometer. It seems there is a transmission path that is not coming directly from the pump to the ground, but maybe through pipes or water itself.
But if we perform periodic/scheduled maintenance, we can say that the signals of the pumps will not be visible in the seismic sensors.
I have noticed that the ITF is not locking anymore. From a very quick glance at the DMS, the problem seems to be the temperature of the WE building out of control causing issues with the local control of the bench (to be confirmed by the experts).
Anyway I have tried to put the ITF in "locked arms" without success, while the North arm locks without troubles.
I have stopped the main Metatron node (ITF_LOCK) and put in auto mode CARM_DARM_LOCK with the status "locked north arm", hoping to keep a good reference for the alignment.
To be investigated tomorrow morning.