To have back the signal in the DAQ (and then in the DMS) we have:
- replaced the application for TCSChillerWI from /virgoApp/PyArtic/v1r1/scripts/PyArtic.py to /virgoDev/Chiller/v3r4/Linux-x86_64-SL6/ChillerApp.exe in the VPM;
- renamed the old configuration file from TCSChillerAux.cfg to TCSChillerWI.cfg;
- renamed the old channels name with the current ones (from TE_Aux_Chiller to TE_WI_Chiller, from TE_Aux_Chiller_Set to TE_Aux_Chiller_Set, from Aux_Chiller_Alarm to Aux_Chiller_Alarm);
- configured the serial bridge with the proper settings: the device has been connected on port 3 of ethadvtcs2 with 9600 Baudrate;
- properly switched off the TCSChillerWI server;
- restart the process from VPM with the new configurations.