Comment to Locking shift (37018)

The actual working point of PR_X and PR_Y is not determined only by the value written on the DSP set point. In recombined mode, the position is adjusted by a control loop adding the output of an integrator to the local error signal. In this way, the correct working point is always recovered, even if the DSP set point is changing.